Rainwater for cooling towers and steam boilers in a university hospital

Client
UZ Gent
Sector
Healthcare
Services
Key figure
Up to 64% of make-up water from rainwater

The challenge

UZ Gent tops up its cooling towers and steam boilers with a mix of groundwater (75%) and mains water (25%). The hospital wanted to replace part of that with rainwater, using the 1,500 m³ buffer tank that was already in place.

What we did

  • Water balance of the cooling towers and steam boilers
  • Simulation of rainwater availability from the existing buffer
  • Design of a treatment system with ultrafiltration (3 m³/h) and a 50 m³ buffer tank
  • Cost-benefit analysis

Results

  • 15,625 to 18,209 m³ of rainwater usable per year
  • 55 to 64% of make-up water covered, up to 80% if only the steam boilers are supplied
  • Payback period of the installation ± 2.3 years