Rainwater or greywater for toilet flushing in new student residences
The challenge
For two new student residences, Ghent University wanted to know how much mains water it could replace with rainwater or treated greywater, and what that would cost.
What we did
- Water balance of both projects
- Dynamic simulation of rainwater use
- Technical and economic comparison of rainwater and greywater reuse
- Comparison of an MBR installation and a constructed wetland
Results
- Toilet flushing accounts for about 22% of total water consumption
- Rainwater can supply ± 84% of the flushing water on average
- Greywater reuse saves ± € 8,000 per year, compared with ± € 3,300 for rainwater
- Payback period ± 3 to 4 years with a constructed wetland, ± 5 years with an MBR
More references
Ghent University: Legionella and domestic hot water
Payback period of 6 to 7 years
Technologies for Legionella prevention, domestic hot water and water softening compared for new and renovated buildings.
Love Tomorrow (Tomorrowland)
Water footprint tracked per edition
A major festival measures its water footprint, sets out actions and tracks the results, edition after edition.
Mutete school campus, Rwanda
100% of the school's demand met by rainwater in an average year
Rainwater as a drinking water source for a school campus with more than 2,200 pupils.
Facing a similar challenge?
Tell us about your site and we'll show you what's possible.